Size of system bonding jumper or bonding conductor (see Appendix B)

1) The size of a field-installed system bonding jumper shall not be less than that determined in accordance with Table 16 based on the ampere rating or setting of the overcurrent device protecting the ungrounded conductors.


2) The size of a bonding conductor installed in accordance with Rule 10-604 at service equipment shall not be less than that determined in accordance with Table 16 based on the allowable ampacity of the largest ungrounded conductor.

3) The size of a field-installed bonding conductor installed at other than service equipment shall not be less than that determined in accordance with Table 16 based on

Δ a) the ampere rating or setting of the overcurrent device protecting the ungrounded conductors; or
b) the allowable ampacity of the largest ungrounded conductor for installations where the size of the circuit conductors is increased to compensate for voltage drop.

4) The size of a field-installed bonding conductor installed with each group of parallel conductors run in separate raceways or cables shall be in accordance with Subrule 3) divided by the number of groups of parallel conductors.

5) Notwithstanding Subrules 2), 3), and 4), the bonding conductor shall not be required to be larger than the current-carrying conductors.

6) A metal raceway that is permitted to be used as a bonding conductor shall be considered to meet the requirements of this Rule.

7) A bonding means that is integral to a cable assembly shall be considered to meet the requirements of this Rule.

Source: Rule 10-616, CSA C22.1:21, Canadian Electrical Code, Part 1 (25th Edition), Safety Standard for Electrical Installations. © 2021 Canadian Standards Association. Please visit store.csagroup.org