Intersection of Built-Up Roofs and Walls other than Masonry
(1) The intersection of built-up roofs with walls clad with other than masonry shall have a cant strip at the intersection.
(2) The roofing membrane shall be mopped over the cant strip referred to in Sentence (1).
(3) Flashing plies shall extend not less than 150 mm up the wall referred to in Sentence (1) behind the sheathing paper.
=